>samit_hota
Back to advisories

Security Advisory · SH-2026-265

HIGHCVE-2023-25914CVSS 8.8OPEN

Danfoss AK-SM 800A Path Traversal Vulnerability Exposes OT Systems

Affected: Danfoss AK-SM 800A Series

Samit Hota·
#kev#danfoss

Supermarket chains, cold storage facilities, and food retail operators rely heavily on Danfoss AK-SM 800A Series system managers to orchestrate complex refrigeration, HVAC, and energy management workflows. A high-severity path traversal vulnerability, tracked as CVE-2023-25914, allows authenticated users to escape designated web directories via the device’s XML interface and read sensitive underlying system files. With a CVSS score of 8.8, this flaw affects all Danfoss AK-SM 800A firmware versions up through 3.3.

Operational Exposure of Danfoss AK-SM 800A Controllers

Danfoss AK-SM 800A units sit directly at the intersection of operational technology (OT) and enterprise management networks. Designed to centralize telemetry and physical control for store infrastructure, these system managers expose web portals and XML management endpoints so operational teams and automated central services can monitor temperatures, adjust setpoints, and retrieve diagnostics.

However, this centralized connectivity makes them attractive target hardware. While current threat telemetry reflects an Exploit Prediction Scoring System (EPSS) score of 1.1% (placing it in the 64.6th percentile of scored vulnerabilities), the attack mechanics present low risk for execution and high risk for system compromise. The underlying CVSS vector (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H) highlights that an attacker with network access needs only low-privilege credentials (PR:L) and low attack complexity (AC:L) to execute the attack over the network without any user interaction.

Technical Breakdown of CVE-2023-25914

The root security failure is categorized under CWE-22 (Improper Limitation of a Pathname to a Restricted Directory). The application’s XML processing service fails to sanitize user-supplied directory path inputs properly. By injecting standard directory traversal sequences—such as ../ or URL-encoded variations—into request parameters accepted by the XML interface, an authenticated low-privilege user can escape the web server root.

In an operational attack scenario, threat actors leverage this exposure through a two-phase attack path:

  1. System File Harvesting: The attacker issues crafted XML requests to read sensitive system configuration files, service account credentials, password hashes, and network configurations residing on the underlying Linux filesystem.
  2. Privilege Escalation and Lateral Movement: Armed with local system secrets or administrative credentials harvested from file reads, the adversary can elevate privileges to full administrative status. This enables direct manipulation of physical setpoints—such as cooling profiles—or turns the controller into an internal jump box to target connected building automation systems.

Because access to these configuration files can indirectly enable system modification and operational disruption, the vulnerability is rated high for impacts to confidentiality, integrity, and availability.

Defense and Mitigation Priorities for CVE-2023-25914

Organizations operating Danfoss AK-SM 800A Series units running firmware 3.3 or earlier should immediately implement the following controls:

  • Upgrade Controller Firmware: Apply updated firmware releases past version 3.3 provided by Danfoss, ensuring the XML endpoint correctly sanitizes directory parameters.
  • Isolate XML and Web Management Interfaces: Ensure AK-SM 800A management interfaces are strictly segregated from public internet access and broader enterprise corporate networks. Enforce access solely through dedicated, multi-factor-authenticated administrative jump hosts or VPN tunnels.
  • Audit and Rotate Credentials: Perform credential rotation for all local and service accounts configured on the AK-SM 800A XML interface. Audit access logs for anomalous GET or XML POST requests containing dot-dot-slash patterns.

Found something similar in your stack?

Let's find out before it becomes an incident.

Book an advisory call